Liebert Datawave Electronic Keyboard User Manual


 
14 Installation Instructions
Table 2 Suggested Minimum Wire Size Data
Voltage kVA
Main Input
1
Output
FLA OPD
Suggested feeder
wire size
2
(AWG) FLA OPD
3
Suggested feeder
wire size
4
(AWG)
208V 100
125
150
200
311
389
466
622
400
500
600
800
2-000*
2-250 kcmil*
2-350 kcmil*
3-300 kcmil*
277
347
416
555
350
450
600
700
500 kcmil
2-0000*
2-350 kcmil*
2-500 kcmil*
240V 100
125
150
200
269
337
404
539
350
450
500
700
500 kcmil
2-000*
2-250 kcmil*
2-500 kcmil*
——
380V 100
125
150
200
170
213
255
340
225
300
350
450
0000
350 kcmil
500 kcmil
2-0000*
152
190
228
304
200
250
300
400
000
250 kcmil
350 kcmil
2-000*
400V 100
125
150
200
162
202
243
323
200
250
300
400
000
250 kcmil
350 kcmil
2-000*
144
180
217
289
200
225
300
400
000
0000
350 kcmil
2-000*
415V 100
125
150
200
156
195
234
312
200
250
300
400
000
250 kcmil
350 kcmil
2-000*
139
174
209
278
175
225
300
350
00
0000
350 kcmil
500 kcmil
480V 100
125
150
200
135
168
202
269
175
225
250
350
00
0000
250 kcmil
500 kcmil
120
150
180
241
150
200
225
300
0
000
0000
350 kcmil
600V 100
125
150
200
108
135
162
216
150
175
225
300
0
00
000
350 kcmil
96
120
144
192
125
150
200
250
1
0
000
250 kcmil
FLA
= Full Load Amps of Datawave Magnetic Synthesizer
OPD
= Overcurrent Protection Device inside Datawave Magnetic Synthesizer
Wire Sizes based on NEC 1996 Table 310-16, using 75°C copper conductor.
*Parallel Feeders per NEC 300-20 and 310-4.
NOTES:
1.
Main input power feeder
should be dedicated feeder direct from service entrance if possible. Ground conductors recommended
to be insulated conductors run with power conductors for increased system performance. Ground conductor minimum size per
NEC Table 250-95. Input power feeder conduit may be used as the safety ground conductor. When conduit is used, adequate
electrical continuity must be maintained at conduit connections to enclosures and throughout conduit run.
2.
Input feeder wire size
listed in
Table 2
is the minimum feeder size recommended. Larger wire size may be required because of
voltage drop or supply overcurrent protection device.
3.
Output OPD's
listed in
Table 2
are the standard sizes for Model CA only. See the unit's specification sheet.
4.
Output feeder wire size
listed in
Table 2
is the minimum feeder size recommended. Larger wire size may be required because of
voltage drop or excessive neutral current (see NEC Table 310-16 notes 8 and 10). For best performance, Synthesizer should be
located as close to the load as practical.