Trane UX1C100A9H41B Microphone User Manual


 
18-CD22D1-8 17
Installer’s Guide
MAXIMUM VENT LENGTH:
MODEL
DIRECT VENT (2 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT AND INLET AIR PIPES (See Notes)
NONDIRECT VENT (1 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT PIPE ONLY (See Notes)
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
*DX1B040A9H21B
60 80 100 130 50 80 80 130
*DX1B060A9H31B
50 80 100 130 50 80 80 130
*DX1B080A9H31B
45 80 100 130 40 80 80 130
*DX1C100A9H41B
NOT ALLOWED 80 100 130 NOT ALLOWED 80 80 130
*DX1D120A9H51B
NOT ALLOWED 15 60 130 NOT ALLOWED 25 70 130
NOTES: * - First letter may be "A" or "T"
1. The INLET AIR of one pipe systems require the installation of a 90° elbow (to prevent dust and debris from falling straight into thefurnace) and a 2 foot
horizontal or vertical straight pipe section connected before or after the elbow.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).
If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception).
The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH
(Vent or Inlet air pipes in two pipe systems).
4. One standard radius 90° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is
equivalent to 6' of 3" pipe. One SHORT/LONG radius 90° elbow is equivalent to 7½' of 2½" pipe, & 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30VENTA termination kit is used, the equivalent length of pipe is 5 feet.
There is zero equivalent length for the BAYVENT200.
6. Pipe adapters are field supplied.
7. 4" pipe may be reduced to 3" for termination with BAYAIR30AVENTA or BAYVENT200 without additional length restriction.
UPFLOW/ HORIZONTAL VENTING TABLE
TABLE 8
MAXIMUM VENT LENGTH:
MODEL
DIRECT VENT (2 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT AND INLET AIR PIPES (See Notes)
NONDIRECT VENT (1 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT PIPE ONLY (See Notes)
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
2" PIPE
& FITTINGS
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
*UX1B040A9H21B
60 80 100 130 50 80 80 130
*UX1B060A9H31B
60 80 100 130 50 80 80 130
*UX1B080A9H31B
50 80 100 130 40 80 80 130
*UX1C100A9H41B
NOT ALLOWED 40 100 130 NOT ALLOWED 40 80 130
*UX1D120A9H51B
NOT ALLOWED 40 100 130 NOT ALLOWED 40 80 130
NOTES: * - First letter may be "A" or "T"
1. The INLET AIR of one pipe systems require the installation of a 90° elbow (to prevent dust and debris from falling straight into thefurnace) and a 2 foot
horizontal or vertical straight pipe section connected before or after the elbow.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).
If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception).
The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH
(Vent or Inlet air pipes in two pipe systems).
4. One standard radius 90° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is
equivalent to 6' of 3" pipe. One SHORT/LONG radius 90° elbow is equivalent to 7½' of 2½" pipe, & 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYVENT100 termination kit is used, the equivalent length of pipe is 5 feet.
There is zero equivalent length for the BAYVENT200.
6. Pipe adapters are field supplied.
7. 4" pipe may be reduced to 3" for termination with BAYAIR30AVENTA or BAYVENT200 without additional length restriction.
Vent only
to outside
Air Inlet
A
A = 2' minimum
DOWNFLOW
FURNACE
Vent only
to outside
Air Inlet
B
A
A (0-2') or greater
B (0-2') or greater
A+B = 2' minimum
UPFLOW FURNACE
SINGLE PIPE VENTING
d