CS 3216 Operators Manual 19
TIMER
LIST
timer’’
Name Scrolling
Display
Parameter Description Value Default Access
Level
THRES TIMER START
THRESHOLD
To set the maximum deviation
between SP and PV before the
timer starts.
Dwell timer and
Programmer only
Off or 1 to 3000 Units above and below setpoint Off
L3
OFF
Control outputs go to zero %
DwEl
Control continues at SP1
SP2
Go to setpoint 2
ENd.T TIMER END
TYPE
To determine the action which
takes place when the timer has
timed out.
Dwell timer and
Programmer only
res
Reset programmer
Conf
SS.SP SOFT START
SETOINT
Sets the threshold below which
the power is limited
SFST timer only
Controller input range 0 Conf
SS.PWR SOFT START
POWER LIMIT
Sets the limit to the power
output during start up
SFST timer only
0 to 100% 0 Conf
res
Reset
run
Running (counting)
hoLd
Running (hold)
T.STAT TIMER
STATUS
Timer status
end
Timed out
L3
Sp
Starts at SP1 (or SP2).
The program must be re-started after a
power failure.
PV
Starts at the current Process value.
The program must be re-started after a
power failure.
sp.rb
Starts at SP1 (or SP2).
The program will continue to run from
the original setpoint value at the last
ramp rate.
servo SERVO MODE Defines the way in which the
programmer starts and how it
recovers from a power failure
Programmer only
pv.rb
Starts at the current Process value.
The program will continue to run from
the current process value and ramp back
at the last ramp rate
sp
Tsp.1 TARGET
SETPOINT 1
To set the target value for the
first setpoint
Controller input range 0 L2
Rmp.1 RAMP RATE 1 To set the rate at which the
setpoint changes to reach
TSP.1
Off, 0:1 to 3000 units per min or hour Off
L2
Dwel.1 DWELL 1 To set the time at which the
setpoint remains at TSP.1
Off, 0:01 to 99:59 hh:mm or mm.ss Off
L2
The above three parameters are repeated for the next 3 program segments, i.e. TSP.2, (3 & 4), RMP.2 (3 & 4), DWEL.2 (3 & 4)
dwell SET TIMER
DURATION
To set the time duration (not
programmer)
0:00 to 99:59 hh:mm or mm.ss 0 L3
T.ELAP ELAPSED
TIME
Time elapsed from when the
timer starts to run
0:00 to 99.59 hh:mm or mm.ss L3 read
only
T.REMN TIME
REMAINING
Time remaining to reach the
set time.
0:00 to 99.59 hh:mm or mm.ss L3
event EVENT
OUTPUTS
Event output operates during
the selected segment
Programmer only
0 = No events operate in any segment
255 -= Events operate in all segments
0 L3
p.cycl PROGRAM
CYCLES
Sets the number of times that a
program is repeated
1 to 100 1 L3
cycle PROGRAM
CYCLE
Displays the current cycle
when the program is running
1 to 100 L3
The timer can be restarted from the Reset condition by changing the time remaining parameter.
CALIBRATION PARAMETER LIST cAL