D9412GV2/D7412GV2 | Operation and Installation Guide | 8.0 On-Board Points
32 Bosch Security Systems, Inc. | 5/05 | F01U003641B
8.4 Point Response Time
The control panel scans both on-board and off-board
point sensor loops every 300 ms. The Debounce
program item in the Point Assignment section of the
software determines point response time by setting the
number of times the control panel scans a point before
generating an alarm.
The debounce count can range from 2 to 15; therefore,
point response time ranges from 600 ms to 4.5 sec. The
Bosch Security Systems default for debounce count is 2.
Increasing debounce might cause missed
alarms. If you increase the debounce count,
detection devices can enter alarm and reset
without exceeding the point response time.
Use a debounce count of 2 for all points except for
Interior Follower points. Program Interior Follower
points as 3. Program door points connected to a
D9210B Access Control Interface Module with a
debounce of 4.
8.5 Wiring Information for Installations
Using the Ademco AB-12
Bell/Housing
1. Disconnect the wire jumper from Terminal 4 to the
inner housing of the Bell Box to prevent a ground
fault condition.
2. Connect wiring between the control and Bell Box
(Figure 11 on page 33).
To use the AB-12 Bell/Housing, place the S3
switch in the disabled (open) position. The EOL
used in the AB-12 Bell/Housing must be a 220 kΩ,
0.5 W resistor.
3. Program Point 8 as 24-hour, alarm on, open, and
short. (PT TYPE 0, PT RESPONSE 0).