A SERVICE OF

logo

®
4
TECHNICAL DATA
STANDBY 500 ekW 625 kVA
60 Hz 1800 rpm 480 Volts
Open Generator Set - — 1800 rpm/60 Hz/480 Volts STANDBY DM6217
Package Performance
Power rating 500 ekW
Power rating @ 0.8 pf 625 kVA
Fuel Consumption
100% load with fan 137.5 L/hr 36.3 Gal/hr
75% load with fan 97.8 L/hr 25.8 Gal/hr
50% load with fan 66.4 L/hr 17.5 Gal/hr
Cooling System
*
Ambient air temperature 50 Deg C 122 Deg F
Air flow restriction (system) .12 kPa 0.48 in. water
Air flow (max @ rated speed for radiator 563 m
3
/min 19,882 cfm
arrangement)
Engine coolant capacity with radiator 72.8 L 19.2 Gal
Exhaust System
Combustion air inlet flow rate 39.2 m
3
/min 1,384.3 cfm
Exhaust stack gas temperature 527.2 Deg C 981 Deg F
Exhaust gas flow rate 111.0 m
3
/min 3,919.9 cfm
Exhaust flange size (internal diameter) 152.4 mm 6.0 in
Exhaust system backpressure (maximum allowable) 6.7 kPa 26.9 in. water
Heat Rejection
Heat rejection to coolant (total) 199 kW 11,317 Btu/min
Heat rejection to exhaust (total) 501 kW 28,492 Btu/min
Heat rejection to atmosphere from engine 76 kW 4,322 Btu/min
Heat rejection to atmosphere from generator 36.47 kW 2,074.04 Btu/min
Alternator
**
Motor starting capability @ 30% voltage dip 855 skVA
Frame 499
Temperature Rise 130 Deg C
Lube System
Lube oil refill volume with filter change for 38.0 L 10.0 Gal
standard sump
Emissions
***
Nox g/hp-hr (not to exceed) < 6.07 g/bhp-hr
CO g/hp-hr (not to exceed) < .48 g/bhp-hr
HC g/hp-hr (not to exceed) < .06 g/bhp-hr
PM g/hp-hr (not to exceed) < .044 g/bhp-hr
*
Ambient capability at 200 m (660 ft) above sea level. For ambient capability at other altitudes, consult your Caterpillar
dealer. Air flow restriction (system) is added to existing restriction from factory.
**
Generator temperature rise is based on a 40 degree C ambient per NEMA MG1-32.
***
Emissions data measurements are consistent with those described in EPA CFR 40 Part 89 Subpart D & E and ISO8178-
1 for measuring HC, CO, PM, NOx. This engine’s exhaust emissions are in compliance with the US EPA and California
nonroad regulations. Data shown is based on steady state operating conditions of 77 deg F, 28.42 in HG and number 2
diesel fuel with 35 deg API and LHV of 18,390 Btu/lb.
17 April 2002 10:34 AM