12. Technical data
Supply voltage:
1x115V +/-10 %, 60Hz.
Motor protection:
The pump requires no external motor protection.
Enclosure class:
Indoor use only, IP42.
CSA Enclosure Type 2.
Insulation class:
F.
Relative air humidity:
Maximum 95 %.
Maximum discharge pressure:
150 psi (10.34 bar).
Inlet pressure:
Sound pressure level:
43 dB (A).
Ambient temperature:
+32 °F (0 °C) to +104 °F (+40 °C).
Liquid temperature:
+36 °F (+2 °C) to +230 °F (+110 °C).
To avoid condensation in the control box and stator,
the liquid temperature must always be higher than
the ambient temperature.
Maximum glycol concentrations:
50 % glycol @ 36 °F (2 °C).
Hydraulic performance change can be expected.
Watt readings:
Accuracy +/-1 Watt.
Flow indicator:
Provides a relative indication of flow — should not
be used in lieu of a flow meter.
Check valve:
Use of check valve may reduce pump hydraulic
performance (up to -10%).
Use check valve in parallel pumping applications.
Curve conditions:
Test liquid: Airless water.
Curves apply to a density of 983.2 kg/m
3
and a
liquid temperature of +140 °F (+60 °C).
All curves show average values and should not be
used as guarantee curves. If a specific minimum
performance is required, individual measurements
must be made.
Curves apply to a kinematic viscosity of 0.474 cSt.
Approximate power usage:
Liquid temperature Min. inlet pressure
167 °F (75 °C) 0.75 psi (0.05 bar)
194 °F (90 °C) 4.06 psi (0.28 bar)
230 °F (110 °C) 15.7 psi (1.08 bar)
Ambient
temperature
[°F (°C)]
Liquid temperature
Min. [°F (°C)] Max. [°F (°C)]
+32 °F
(0 °C)
+36 °F
(+2 °C)
+230 °F
(+110 °C)
+50 °F
(+10 °C)
+50 °F
(+10 °C)
+230 °F
(+110 °C)
+68 °F
(+20 °C)
+68 °F
(+20 °C)
+230 °F
(+110 °C)
+86 °F
(+30 °C)
+86 °F
(+30 °C)
+230 °F
(+110 °C)
+95 °F
(+35 °C)
+95 °F
(+35 °C)
+194 °F
(+90 °C)
+104 °F
(+40 °C)
+104 °F
(+40 °C)
+158 °F
(+70 °C)
In domestic hot-water system, it is
recommended to keep the liquid
temperature below +149 °F (+65 °C) to
eliminate the risk of lime precipitation.
Speed setting Min. Max.
High fixed speed III 39W 45W
Medium fixed speed II 15W 30W
Low fixed speed I 5W 8W
Constant pressure 8W 45W
Constant pressure 14W 45W
Constant pressure 22W 45W
AutoADAPT 5W 45W