40
Measuring Points and Instruments
(Reference Measured Value)
<Across L
1
-L
2
, L
2
-L
3
and L
3
-L
1
>
Moving-iron type AC voltmeter
Within permissible AC voltage
fluctuation Refer to Page 40
1
<L
1,
L
2
, and L
3
line currents>
Moving-iron type AC ammeter
1
At R, S and T, and across R-S,
<At L
1
, L
2
and L
3
, and across
Electrodynamic type single-
1
11
+
12
+
13
1
Calculate after measuring power supply voltage, power supply side current and power supply side
×
1
1
1
1
2
Rectifier type AC voltmeter
(Note 1) (Not moving-iron
Difference between phases is
within
±
1% of maximum output
2
Moving-iron type AC ammeter
Current should be equal to or less
than rated inverter current.
Difference between phases is
2
At U, V and W, and across U-V
Electrodynamic type single-
2
21
+
22
2-wattmeter method (or 3-
2
Calculate in similar manner to power supply side power factor.
×
2
2
2
2
Across P-N< Across + and - >
Moving-coil type (such as
×
1
“5” is
common.
(without frequency meter)
DC8V
T1
T2
Pulse width T1:
Adjusted by Pr.900
Pulse cycle T2: Set by Pr.55
(Valid for
frequency
monitoring only)
(without frequency meter)
Across STF, STR, RH, RM, RL,
Moving-coil type (Tester, etc.
resistance: 50k
Ω
or larger)
SD is common.
Continuity check (Note 2)
<At OFF> <At ON>
Across A-C: Discontinuity Continuity
Across B-C: Continuity
Discontinuity
Note 1. Accurate data will not be obtained by a tester.
2. When Pr. 195 "A, B, C terminal function selection" setting is positive logic.