FUNCTION OVERVIEW
20
4.2 Setting the Running Frequecy
The following table lists the functions which can be executed from the programmable logic controller in the CC-Link system:
Operation Mode
Control Location Item
PU operation External operation CC-Link operation
Operation command Disallowed Disallowed Allowed
Running frequency setting Disallowed Disallowed Allowed
Monitoring Allowed Allowed Allowed
Parameter write Disallowed (*3) Disallowed (*3) Allowed (*3)
Parameter read Allowed Allowed Allowed
Inverter reset Disallowed Disallowed Allowed (*1)
Error reset at inverter fault
(RY1A)
Allowed (*1) Allowed (*1) Allowed (*1)
User program
Stop command (*2) Disallowed Disallowed Allowed
Inverter reset terminal Allowed Allowed Allowed
Operation command Disallowed Allowed Allowed (*4)
Control circuit
terminal
Frequency setting Disallowed Allowed Allowed (*4)
(
*
1) At occurrence of a communication error, the inverter cannot be reset from the computer. (For inverter reset, refer
to the inverter manual.)
(
*
2) As set in Pr. 75.
(
*
3) As set in Pr. 77.
Values can be written to Pr. 4 to Pr. 6, Pr. 22, Pr. 24 to Pr. 27, Pr. 52 to Pr. 56, Pr. 72, Pr. 232 to Pr. 239 during
operation.
(For full information, refer to the inverter manual.)
(
*
4) As set in Pr. 338 and Pr. 339
Note 1. The inverter goes into the external operation mode if it is reset from the PLC in the CC-Link operation mode.
The setting of "1" in Pr. 340 (link start mode) selects CC-Link operation mode.