Charging
Cycle Applications: Limit initial current to 19.5A. Charge until battery voltage (under
charge) reaches 13.90 to 14.20 volts at 68°F (20°C). Hold at 13.90 to 14.20
volts until current drops to under 650mA. Battery is fully charged under these
conditions, and charger should be disconnected or switched to “oat” voltage.
“Float” or “Stand-By” Service: Hold battery across constant voltage source of 13.50
to 13.80 volts continuously. When held at this voltage, the battery will seek its own
current level and maintain itself in a fully charged condition.
Note: Due to the self-discharge characteristics, it is imperative that they be charged
within 6 months of storage, otherwise permanent loss of capacity might occur as a
result of sulfation.
Chargers
Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH.
Please refer to the Charger Selection Guide in our specication sheets for “C-Series
Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our
Technical department for advice if you have difculty in locating suitable models.
Capacity Retention Ratio (%)
Standing Period (Months)
100
80
60
40
0
0 2 4 6 8 10 12 14 16 18 20
40
o
C
(104
o
F)
30
o
C
(86
o
F)
20
o
C
(68
o
F)
5
o
C
(41
o
F)
Chargingisnot
necessary unless
100% of capacity
is required.
Chargingbefore
use is necessary
to help recover
full capacity.
Chargemayfail
to restore full
capacity. Do not
let batteries reach
this state.
100
80
60
40
20
0
0 1 2 3 4
Ambient Temperature 20˚C (68˚F)
Float Charging Voltage
2.25 - 2.30 V/Cell
Retention Capacity (%)
Years
Discharge Characteristics
Discharge Time vs. Discharge Current
Shelf Life & Storage
Life Characteristics in Stand-By Use
Life Characteristics in Cyclic Use
DCG12-65 12 Volt 65 AH
®
CUSTOMER SERVICE
Tel: +1-619-661-2030
Fax: +1-619-661-3648
customer-service@power-sonic.com
INTERNATIONAL SALES
Tel: +1-650-364-5001
Fax: +1-650-366-3662
battery@power-sonic.com
DOMESTIC SALES
Tel: +1-619-661-2020
Fax: +1-619-661-3650
national-sales@power-sonic.com
TECHNICAL SUPPORT
Tel: +1-619-661-2020
Fax: +1-619-661-3648
support@power-sonic.com
Contact Information
www.power-sonic.com
Capacity (%)
120
500
100%
DOD
50%
DOD
30%
DOD
20%
DOD
1000 1500 2000 2500 3000
100
80
60
40
20
0
Number of Cycles (Time)
Further Information
Please refer to our website www.power-sonic.com for a complete range of useful
downloads, such as product catalogs, material safety data sheets (MSDS), ISO
certication, etc..
0309 1M
10
9
8
7
6
5
4
3
2
60
50
40
30
20
10
8
6
0 1 2 4 6 7.5 9 11.5 24 45 73 105
Discharge Time
Discharge Current (A)
min h
0ºC
(32ºF)
40ºC
(104ºF)
25ºC
(77ºF)
13
12
11
10.8
10.5
9.6
9
7.8
Loading Voltage (V)
Discharge Time
0 3
min h
35 510 10 2016 30 60 2
70A
40.3A
17.2A
11.6A
6.58A
3.5A