MD Cooling Tower
/
Engineering Data : Schematic
13
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley UPDATE web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia.
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
Model
note 2
Nominal Tons
note 3
Motor
kW
dBA
1.5m from air
inlet face
Dimensions
Design
Operating
Weight
kg
Shipping Weight
kg
H A Weight/Cell
Heaviest
Section
MD5010PAC2L
248
11 81
3628 2515 3906 2102 1052
MD5010PLC2L 249 11 80
MD5010QAC2L 269 15 81
MD5010QLC2L 270 15 80
MD5010RAC2L 286 18.5 81
MD5010RLC2L 289 18.5 80
MD5010PAD2L 279 11 81
3932 2820 4069 2265 1213
MD5010PLD2L 280 11 80
MD5010QAD2L 304 15 81
MD5010QLD2L 305 15 80
MD5010RAD2L 325 18.5 81
MD5010RLD2L 329 18.5 80
MD5010PAF2L 293 11 81
4237 3124 4256 2453 1376
MD5010PLF2L 294 11 80
MD5010QAF2L 317 15 81
MD5010QLF2L 318 15 80
MD5010RAF2L 341 18.5 81
MD5010RLF2L 346 18.5 80
MD5010SAF2L 360 22 81
MD5010SLF2L 362 22 81
MD5010 MULTICELL