7. Instructions
Data table:
Register Data contents Signal direction
RW100 #0 Operating frequency
Read
RW101 #0 Output terminal status
Read
RW102 No use
RW103 No use
RW104 #1 Operating frequency
Read
RW105 #1 Output terminal status
Read
RW106 No use
RW107 No use
RW176 #19 Operating frequency
Read
RW177 #19 Output terminal status
Read
RW178 No use
RW179 No use
The data format for the operating frequency register is 0.01 Hz units. For example, if it is 60 Hz, the
corresponding register data is 6000.
The bit assignment of the output terminal status register is as follows. For details, refer to your
Inverter manual.
FEDCBA9876543210
OUT1 (f130)
OUT2 (f131)
FL (f132)
R1 (f133)
R2 (f134)
OUT3 (f135)
OUT4 (f136)
ALM0
ALM1
ALM2
ALM3
Example operation:
The current operating frequency and the output terminal status of the #0 Inverter are stored in RW100
and RW101 respectively.
If the #0 Inverter is operating at 55 Hz, the data 5500 is stored in RW100. If the OUT2 terminal of the
#0 Inverter is ON, the bit 1 of RW101 (R1011) becomes 1.