CONDITION POSSIBLE CAUSE
REMEDY/
REFERENCE
SECTION
3.3 ALTERNATING CURRENT GENERATOR (CONTINUED)
Overheating
Generator overloaded
Clogged ventilating screens
High temperature surrounding generator
Insufficient air circulation
Unbalanced load
Dry bearing
Check
Clean
Section 4.4.5
Section 4.5.1
Balance
Section 4.5.1/
4.5.3
Mechanical Noise
Bad bearing
Rotor scrubbing on stator
Loose laminations
Loose or misaligned coupling
Section 4.5.1/
4.5.3
Section 4.5.1/
4.5.3
Section 4.5.4/
Replace
Section 4.5.4
Generator frame produces shock
when touched
Static charge
Grounded armature of field coil
Check ground to
frame
Section 4.5.4/
Replace
3.4 AUTO RE-START OPTION
When the Ignition switch is placed in
the RUN position, nothing happens--
no lights illuminate
W ait 30 seconds for intake heater to be activated
Coolant level below the low coolant sensor
Relay defective
Ignition switch defective
3 amp Fuse is bad
Loose connector on module
Auto restart module is bad
Miswired connectors
Wait
1.10.j.
Check/Replace
Check/Replace
Switch
Check and
Replace Fuse
T ighten
connector
Check for 12
volts at Pin 4/
Replace module
Check/Correct
wiring
Alarm sounds, but engine does not
crank
No voltage at Pin 2 of the connector
Check Starter Solenoid
Auto restart module is bad
T race/Correct
See 3.1.1
Replace module
Engine starts, but the starter does
not disengage
Speed Sensor wiring loose
Speed Sensor is bad
Auto restart module is bad
Check/Correct
Replace
Replace module