A SERVICE OF

logo

TP-6200 10/12 131Section 2 Operation
Local Programming Mode On
2.8.15 Menu 15—Protective Relays (PR)
Menu 15 provides the necessary protective relays for
units with the optional paralleling protection feature. If
the generator set personality profile did not include the
paralleling option this menu will not appear on the
display. Available with PD-Series switchgear only.
Menu 15—Protective Relays
Menu 15 Displays with Key Entries
Displays the overvoltage % value. When required, use t he numeric
keys to enter the desired overvoltage % value and press the Enter
key.
Key
Entry Display Description
Input a menu number.
MENU 15
PROTECTIVE RELAYS
PR OVERVOLTAGE
?% #VAC
MAIN MENU NUMBER 15
ENTER MENU NO. 1--15
Press the Enter key.
Displays the menu number and name.
Displays the corrected overvoltage % value.
PR OVERVOLTAGE
#% #VAC
Displays the overvoltage time delay. When required, use the numeric
keys to enter the desired time delay value and press the Enter key.
TIME DELAY
?SEC
Displays the corrected overvoltage time delay value.
TIME DELAY
#SEC
PR OVERVOLTAGE
?% #VAC
Returns the user to the overvoltage % value display.
Displays the undervoltage % value. When required, use t he numeric
keys to enter the desired undervoltage % value and press the Enter
key.
PR UNDERVOLTAGE
?% #VAC
Displays the corrected undervoltage % value.
PR UNDERVOLTAGE
#% #VAC
Displays the undervoltage time delay. When required, use the
numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY
?SEC
Displays the corrected undervoltage time delay value.
TIME DELAY
#SEC
PR UNDERVOLTAGE
?% #VAC
Returns the user to the undervoltage % value display.
Displays the overfrequency % value. When required, use t he
numeric keys to enter the desired overfrequency % value and press
the Enter key.
PR OVERFREQUENCY
?% #HZ
Displays the corrected overfrequency % value.
PR OVERFREQUENCY
#% #HZ
Displays the overfrequency time delay. When required, use the
numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY
?SEC
Displays the corrected overfrequency time delay value.
TIME DELAY
#SEC
PR OVERFREQUENCY
?% #VAC
Returns the user to the overfrequency % value display.