affecting that input. If an input is disabled, the word “Off”
immediately follows the number recited for that input.
For example, input 3 is configured as a normally open, dry
contact input. During the Status Report:
• If disabled, the Model 1108 recites:
“Number 3—Off—OK,” for input 3.
• If enabled, the Model 1108 recites:
“Number 3—OK,” for input 3.
In another example, input 2 is configured as a temperature input.
The current temperature is 76 degrees. During a Status Report:
• If disabled, the Model 1108 recites:
“Number 2—Off—76 degrees—OK.”
• If enabled, the Model 1108 recites:
“Number 2—76 degrees—OK.”
5.3 Input Recognition Time
The Input Recognition Time is the length of time an alert
condition must be present before a valid alarm exists and dial-out
is activated. This time period is programmable, from 0 minutes, 0
seconds (for immediate response) up to a period of 272 minutes, 0
seconds. If an alert condition begins and then clears within the
established Recognition Time, no dial-out will occur. When an
alert condition continues beyond the programmed Recognition
Time, the Model 1108 initiates dial-out. The default setting for
Input Recognition Time is 0 minutes, 3 seconds.
5.3.1 Programming Input Recognition Time
1. Press SET.
2. Press RECOGNITION TIME.
Sensaphone
®
Model 1108 User’s Manual
70