A SERVICE OF

logo

64
13.7.1 Command Parameters
Parameter
Bit Function Bank Mask Adjustment Range Multiplier
0001 word Frequency command 0 FFFF
0.00 400.00Hz
Actual frequency will be limited by
LL, UL and Fmax.
0.01
0002 0 RUN command 0
0: Stop
1: Run
1 Reserved
2
Forward reverse run
selection
0: reverse
1: forward
3 Acc/dec #1 / #2
selection
0: Acc / dec #1
1: Acc / dec #2
4 Reserved
5 Reserved
6 Reserved
7 Jog mode selection 0: Normal (acc/dec mode)
1: Jog mode
8 Feedback control 0: Feedback valid
1: Feedback invalid
9 Compulsory DC
injection braking mode
0: No compulsory DC injection
braking
1: Compulsory DC injection
below DC INJECTION
START FREQUENCY
A Fundamental
parameter switching
0: V/F #1
1: V/F #2
B Gate block command
(coast stop command)
0: Normal
1: Gate block
C Emergency off
command
0: Does nothing
1: Emergency off
D Reset command
(trip clear)
0: Does nothing
1: Reset
E Reserved
F Reserved
0003 word RS232 command /
frequency selection
0 0003 0000: FREQUENCY MODE
SELECTION, COMMAND
MODE SELECTION
settings
0001: RS232C commands valid
0002: RS232C frequency valid
0003: RS232C commands and
frequency valid
0004 word Preset speed run
command
0 000F 0000: Output frequency
selected by FREQUENCY
MODE SELECTION
0001 000F: speeds 1 15