11.2 THREE-WIRE START/STOP CONTROL
NOTES:
1. Program TB-13C (Parameter 12) for START FORWARD (05).
2. If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND REVERSE
(02), and program TB-13A (Parameter 10) for START REVERSE (06).
3. Momentarily close TB-13C to TB-11 to START in the forward direction, or close TB-13A to
TB-11 to START in the reverse direction. Momentarily open TB-1 to TB-11 to STOP the drive.
4. For speed pot control, set STANDARD SPEED SOURCE (Parameter 05) to SPEED POT (03).
STOP
SPEED POT COMMON
SPEED POT INPUT
SPEED POT POWER SUPPLY
TB-13A FUNCTION SELECT
(START REVERSE)
TB-13B FUNCTION SELECT
TB-13C FUNCTION SELECT
(START FORWARD)
OPEN-COLLECTOR OUTPUT
DIGITAL INPUT REFERENCE
MOMENTARY
STOP CONTACT
SPEED
POT
MOMENTARY
START CONTACT
REV FWD
1
3
5 6 1 1 13A 13B 1413C
WARNING!
Hazard of electrical shock! The SM-Basic control terminals are not isolated from line voltage!
Line voltage is present between the control terminals and ground. Do not touch!
Disconnect input power and wait three minutes before making connections to the control terminals.
Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the
control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a
dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel.