![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/5/ab/5abdb5bd-1c0a-4842-85ef-70d81c5b4833/5abdb5bd-1c0a-4842-85ef-70d81c5b4833-bg1a.png)
22
NOTE 1: Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.
NOTE 2: If LINE VOLTAGE is set to LOW, maximum setting is 150%.
FACTORY
FACTORYFACTORY
FACTORY
NO.
NO.NO.
NO. PARAMETER NAME
PARAMETER NAMEPARAMETER NAME
PARAMETER NAME RANGE OF ADUSTMENT
RANGE OF ADUSTMENTRANGE OF ADUSTMENT
RANGE OF ADUSTMENT DEFAULT
DEFAULTDEFAULT
DEFAULT
(NOTE 1)
14
1414
14 CONTROL
CONTROLCONTROL
CONTROL TERMINAL STRIP ONLY (01), TERMINAL STRIP
REMOTE KEYPAD ONLY (02) ONLY (01)
17 ROTATION FORWARD ONLY (01), FORWARD
FORWARD AND REVERSE (02) ONLY (01)
18 TIME RANGE SELECT x0.1 (01), x1.0 (02), x10.0 (03) x1.0 (02)
19 ACCELERATION TIME 0.1 - 990 SEC 20 SEC
20 DECELERATION TIME 0.1 - 990 SEC 20 SEC
21 DC BRAKE TIME 0.0 - 990 SEC 0 SEC
22 DC BRAKE VOLTAGE 0 - 30 % 0 %
23 MINIMUM FREQUENCY 0 - MAXIMUM FREQUENCY 0 Hz
24 MAXIMUM FREQUENCY MINIMUM FREQUENCY - 99 Hz 60 Hz
25 CURRENT LIMIT 30 - 180 % (NOTE 2) 180 %
26 MOTOR OVERLOAD 30 - 100 % 100 %
27 BASE FREQUENCY 25 - 99 Hz 60 Hz
28 FIXED BOOST 0 - 30 % 1 %
29 ACCEL BOOST 0 - 20 % 0 %
30 SLIP COMPENSATION 0.0 - 5.0 % 0 %
31-37 PRESET SPEEDS 0 - MAXIMUM FREQUENCY 0 Hz
38 SKIP BANDWIDTH 0 - 10 Hz 0 Hz
42 ACCEL / DECEL #2 0.1 - 990 SEC 20 SEC
44 PASSWORD 00 - 99 25
47 CLEAR HISTORY MAINTAIN (01), CLEAR (02) MAINTAIN (01)
48 PROGRAM USER SETTINGS (01), OEM SETTINGS (02), USER
SELECTION RESET OEM (03), RESET 60 (04), SETTINGS (01)
RESET 50 (05), TRANSLATE (06)
50 FAULT HISTORY (VIEW-ONLY) (N/A)
51 SOFTWARE CODE (VIEW-ONLY) (N/A)
52 DC BUS VOLTAGE (VIEW-ONLY) (N/A)
53 MOTOR VOLTAGE (VIEW-ONLY) (N/A)
54 LOAD (VIEW-ONLY) (N/A)
55 SPEED POT INPUT (VIEW-ONLY) (N/A)
57 TB STRIP STATUS (VIEW-ONLY) (N/A)
58 KEYPAD STATUS (VIEW-ONLY) (N/A)