Intel SC5000 Recording Equipment User Manual


 
Safety Guidelines 7
OVERCURRENT PROTECTION: The server is designed for an AC line
voltage source with up to 20 amperes of overcurrent protection. If the
power system for the equipment rack is installed on a branch circuit
with more than 20 amperes of protection, you must provide
supplemental protection for the server. If more than one server is
installed in the rack, the power source for each server must be from a
separate branch circuit. The overall current rating of a server
configured with a 350 watt 1+1 power supply is under 12 amperes.
CAUTIONS
Temperature: The operating temperature of the server, when installed in an
equipment rack, must not go below 5 °C (41 °F) or rise above 35 °C (95 °F).
Extreme fluctuations in temperature can cause a variety of problems in your
server.
Ventilation: The equipment rack must provide sufficient airflow to the front
of the server to maintain proper cooling. It must also include ventilation
sufficient to exhaust a maximum of 2000 Btu's per hour for the server. The
rack selected and the ventilation provided must be suitable to the
environment in which the server will be used.