
The cooling coil shall have a minimum of _____ sq. ft.
(sq. m) face area, _____ rows deep. The coil shall be
controlled by a modulating control valve. The chilled
water coil shall be designed for closed-loop applica-
tions using properly maintained water. It shall be
configured as an (A) (V) frame and be constructed of
copper tubes and aluminum fins and have a maxi-
mum face velocity of _____ ft. per minute (m/s) at
_____ CFM (CMH). The water circuit shall be
designed to distribute water into the entire coil face
area. The coil shall be supplied with _____ °F (°C)
entering water temperature, with a _____ °F (°C)
temperature rise. The coil shall be supplied with
_____ GPM (m/s) of chilled water and the pressure
drop shall not exceed _____ PSI (kPa). The coil
assembly shall be mounted in a stainless steel con-
densate drain pan.
3-Way Chilled Water Valve (Standard)
The water circuit shall include a 3-way modulating
valve. The microprocessor control shall position the
valve in response to room conditions. Cooling capac-
ity will be controlled by bypassing chilled water
around the coil.
2-Way Chilled Water Valve (Optional)
The water circuit shall include a 2-way modulating
valve. The microprocessor control shall position the
valve in response to room conditions. The minimum
close-off pressure of the valve/actuator assembly
shall be _____ PSI (kPa).
Design Pressure
The chilled water circuit shall be designed for a pres-
sure of [(150 PSI (1034 kPa)) (400 PSI (2758 kPa))].
Flow Switch (Optional)
The flow switch shall activate the alarm system
should the chilled water supply be interrupted. The
switch shall be factory mounted and wired.
(For detailed Guide Specifications on these products,
refer to information posted at www.liebert.com)
SiteScan Web System
SiteLink Module
OpenComms Nform
OpenComms NIC & Web Card (OC-NIC &
OC-Web Card)
Environmental Discrete Outputs Card
(ENV-DO)
Remote Contact Monitor
• RCM4
Autochangeover Controllers
• AC3
• RAC2-8
Universal Monitor
Leak Detection
• Direct Read Module
• Zone Sensor
• Spot Sensor
Install environmental control units in accordance
with manufacturer’s installation instructions. Install
units plumb and level, firmly anchored in locations
indicated, and maintain manufacturer’s recom-
mended clearances.
Install and connect electrical devices furnished by
manufacturer but not specified to be factory mounted.
Furnish copy of manufacturer’s electrical connection
diagram submittal to electrical contractor.
Install and connect devices furnished by manufac-
turer but not specified to be factory mounted. Fur-
nish copy of manufacturer’s piping connection
diagram submittal to piping contractor.
Connect water supply and drains to air conditioning
unit. Provide pitch and trap as manufacturer’s
instructions and local codes require.
Start up environmental control units in accordance
with manufacturer’s start up instructions. Test con-
trols and demonstrate compliance with requirements.
DISCONTINUED
PRODUCT