28 HP StorageWorks Disk Array XP128: Site Preparation Guide
3. The clearance on the front left side must be 280 mm or wider in order
to open the front door.
4. Dimensions in parentheses show the allowable range of floor cutout
sizes. The preferred position of the floor cutout is in the center of the
array. However, the position may be off-center as long as the cutout
allows smooth entrance of all external cables and is within the allowable
range.
5. This dimension varies depending on the floor cutout dimensions.
Minimum service clearances
The minimum service clearance is the smallest amount of additional floor
space surrounding the array required in order to access the disk array for
servicing. This space should be reserved for the disk array and never used
for storage.
The minimum service access is:
Rear: 800 mm (31.5 in)
•Side: 0 mm
Front: 800 mm (31.5 in)