Preparing for installation 33
The table below lists the basic AC power requirements for a 50-amp,
single-phase XP128.
The table below lists the basic AC power requirements for a 30-amp,
single-phase XP128.
Parameter
Nominal Rated Voltage (VAC)
200 208
*
220 230 240
Minimum operating voltage (VAC) 184 191 202 212 221
Maximum operating voltage (VAC) 212 220 233 244 254
Rated line current per power cord
(amps RMS)
16.2 15.1 14.9 14.3 13.8
Number of power cords 2 2 2 2 2
Recommended circuit breakers (amps) 50 50 50 50 50
Number of circuit breakers 2 2 2 2 2
Dropout carry-through time at
minimum line voltage (ms)
30 30 30 30 30
* 60 Hz only.
Parameter
Nominal Rated Voltage (VAC)
200 208
*
220 230 240
Minimum operating voltage (VAC) 184 191 202 212 221
Maximum operating voltage (VAC) 212 220 233 244 254
Rated line current per power cord
(amps RMS)
10.2 9.5 9.4 9.0 8.7
Number of power cords 4 4 4 4 4
Recommended circuit breakers (amps) 30 30 30 30 30
Number of circuit breakers 4 4 4 4 4
Dropout carry-through time at
minimum line voltage (ms)
30 30 30 30 30
* 60 Hz only.