Appendix B Installation of Remote Termination Panels (RTPs) - Analog Input
Revision 5 HC900 Hybrid Controller Installation and User Guide 185
9/03
8 Point Analog Input
Step Action
3 Set DIP switch positions SW1 through SW8.
Set each input’s DIP switch positions according to the input type. Refer to Figure 61 (Step 4) to determine
which switch corresponds to which input. If an input is not used, set its DIP switch positions to OFF.
SW9
Volt, millivolt:
1 2
O
N
1 2
O
N
1 2
O
N
Ohms:
1 2
O
N
1 2
O
N
1 2
O
N
Transmitter:
1 2
O
N
1 2
O
N
Milliamp:
1 2
O
N
1 2
O
N
RTD:
1 2
O
N
1 2
O
N
1 2
O
N
SW9 is the red power switch for 24 volt supply. Module RIUP is not affected by using the RTP.
See page 190 for RTP internal schematic.
4 Connect field wiring.
Refer to Figure 61 through Figure 67 for field wiring. Any input type can be wired to any of the 8 inputs. After
wiring, double check DIP switches are set correctly for each input type (Step 3).
Fuses: 80mA Time lag
Wickmann part
#3740080041
UL/CSA approved