…4 CONFIGURATION MODE
4.3 Basic Hardware and Configuration (Level 3) – Fig. 4.3
4.3.1 Hardware Assignment and Input Type
Level 3
Note. To select this frame from anywhere in this
level, press the
key for a few seconds.
'ABCD' Settings
The first character (A, B, C or D) identifies the
parameter to be changed. The current setting is
indicated by a flashing letter. Parameter options are
shown in Fig. 4.3.
A = Hardware configuration
b = Input type and range
C = Temperature units
d = No. of decimal points
Note. The temperature ranges default to their
maximum values when the input type is changed.
Continued on page 22.
LEVEL3
B 1KC0
A 1KC0
C 1KC0
d 1KC0
E 1203
units/sec
counter factor
actual engineering flow rate
flow range time units (in seconds)
Information.
Count High Calculation
Convert flow rate into units/sec =
Count High = resultant must be >0.001 and <99.999pps.
Counter factor is the engineering value of the least significant digit shown on
the totalizer display – see Section 4.3.3.
Totalizer Count Pulse
The totalizer count pulse is on for a preset time of 250ms and off for a minimum
of 250ms.