5 INSTALLATION…
5.4.3 Logic Output
18V DC at 20mA
Min load 900
Isolated from Analog Input (not
isolated from Retransmission
Output). Dielectric strength –
500V d.c. for 1 minute.
5.4.4 Control or Retransmission
Analog Output
Max. load 15V (750 at 20mA)
Isolated from Analog Input (not
isolated from Logic Oouput).
Dielectric strength - 500V d.c. for
1 minute.
10 9 8
Switched
Supply
NO
C
NC
Terminal Block
Suppression
component
(B9303)
Load Load
11 7
Fig. 5.5 Fitting Arc Suppression
Components
5.3 Electrical Connections –
Figs. 5.5 and 5.6
Warning. Before making
any connections, ensure that the
power supply, any powered control
circuits and high common mode
voltages are switched off.
Note. If it is not possible to
avoid strong electrical and
magnetic fields, screened cables
within earthed/grounded metal
conduit must be used.
5.4 Relays, Arc Suppression
and Outputs
5.4.1 Relay Contact Ratings
Relay contacts are rated at:
115/230V AC at 5A (non-inductive)
250V DC 25W max.
5.4.2 Arc Suppression - Fig. 5.5
Arc suppression components are fitted
to relays 2 and 3 only. If relay 1 is
required to switch inductive loads, the
arc suppression component supplied
must be fitted across the contacts
used.