A SERVICE OF

logo

14
INSTALLATION AND WIRING
*1: Terminals PR and PX are provided for the FR-A520-0.4K to 7.5K, FR-A540-0.4K to 7.5K.
*2: Low indicates that the open collector outputting transistor is on (conducts).
High indicates that the transistor is off (does not conduct).
*3: Not output while the inverter is reset.
Type Symbol Terminal Name Description
Analog
Frequency setting
10E
Frequency setting
power supply
10VDC, permissible load
current 10mA
When the frequency setting potentiometer is
connected in the factory-set state, connect it to
terminal 10.
When it is connected to terminal 10E, change the
input specifications of terminal 2.
10
5VDC, permissible load current
10mA
2
Frequency setting
(voltage)
By entering 0 to 5VDC (0 to 10VDC), the maximum output frequency is reached at 5V
(or 10V) and I/O are proportional. Switch between input 0 to 5VDC (factory setting)
and 0 to 10VDC from the operation panel. Input resistance 10k. Maximum
permissible voltage 20V.
4
Frequency setting
(current)
By entering 4 to 20mADC, the maximum output frequency is reached at 20mA and I/O
are proportional. This input signal is valid only when the AU signal is on. (Voltage input
is made invalid) Input resistance 250. Maximum permissible current 30mA.
1
Auxiliary frequency
setting
By entering 0 to ±5VDC or 0 to ±10VDC, this signal is added to the frequency setting
signal of terminal 2 or 4. Switch between input 0 to ±5VDC and 0 to ±10VDC (factory
setting) from the operation panel. Input resistance 10k. Maximum permissible
voltage ±20V.
5
Frequency setting
input common
Common to the frequency setting signal (terminal 2, 1 or 4) and analog output terminal
AM. Do not earth.
Output signals
Contact
A, B, C Alarm output
1 contact output indicating that the output has been stopped by
the inverter protective function activated.
230VAC 0.3A, 30VDC 0.3A. Alarm: discontinuity across B-C
(continuity across A-C), normal: continuity across B-C
(discontinuity across A-C).
Output terminal
function selection
(Pr. 190 to
Pr. 195) change
terminal functions.
Open collector
RUN Inverter running
Switched low when the inverter output frequency is equal to or
higher than the starting frequency (factory set to 0.5Hz, variable).
Switched high during stop or DC injection brake operation (*2).
Permissible load 24VDC 0.1A
SU Up to frequency
Switched low when the output frequency has reached within
±10% of the set frequency (factory setting, variable). Switched
high during acceleration, deceleration or stop (*2). Permissible
load 24VDC 0.1A.
OL Overload alarm
Switched low when the stall prevention function has caused stall
prevention to be activated. Switched high when stall prevention is
reset (*2). Permissible load 24VDC 0.1A.
IPF
Instantaneous power
failure
Switched low when instantaneous power failure or undervoltage
protection is activated (*2). Permissible load 24VDC 0.1A.
FU Frequency detection
Switched low when the output frequency has reached or
exceeded the detection frequency set as appropriate. Switched
high when below the detection frequency (*2). Permissible load
24VDC 0.1A
SE
Open collector output
common
Common to the RUN, SU, OL, IPF and FU terminals.
Pulse
FM For meter
One selected from 16
monitoring items, such as
output frequency, is output. (*3)
The output signal is
proportional to the magnitude
of each monitoring item.
Factory setting of output item:
Frequency permissible load current 2mA
1440 pulses/s at 60Hz
Analog
AM Analog signal output
Factory setting of output item:
Frequency output signal 0 to 10VDC
Permissible load current 1mA
Communication
RS-485
 PU connector
With the operation panel connector, communication can be made through RS-485.
Conforming standard : EIA Standard RS-485
Transmission format : Multi-drop link
Communication speed : Maximum 19200 bps
Overall length : 500m