7532 Commissioning
Function "dip table handl." (036)
Use this function to enter the dip value (level or distance) which will correct the mea-
surement values.
Selection:
new point
edit point
•store point
delete point
•return
•next point
•previous point
General procedure:
To enter a new point into the dip table, use
"new point" to enter the value (pairs),
"store point" to sort the new value (pairs),
"return" to go to the dip table mode and
"table on" to activate the dip table.
new point
You can enter a new point. A suggested value is displayed for the measured variable, the
dip value of the current level or the distance. With semi-automatic inputs, the current
level or the current remaining fill height is displayed as proposed dip value. The new
value pair can be altered without selecting the
"edit point" parameter.
If the table is full, you can still select this parameter. In this case, the number of free
table entries stands at minimum value (=0).
edit point
The displayed value pair can be changed. Only the dip value can be changed with semi-
automatic input mode.
Caution!
To accept the value pair in the table, confirm it with "store point".
store point
The displayed value pair is sorted in the table.
Note!
For sorting, the following criteria must be met:
Measured variables may not be equal but have different dip values.
A measured variable available in the table is recognized as equal when it is closer than
1 mm to the sorting value.
After successful sorting, the setting remains at "edit point" and the number of free
table entries is decremented.
Caution!
If the value cannot be sorted, the setting remains at the previous menu option. No
warning or error message is generated. However, the number of remaining table entries
is not decremented.