Commissioning Radar Tank Gauge
70 Installation and Operations Manual
6.7 Mounting calibration with the ToF Tool
To carry out the basic setup with the ToF Tool operating program, proceed as follows:
Start the ToF Tool operating program and establish a connection
Select the "mounting calibr." function group in the navigation bar
The following display appears on the screen:
Mounting calibration step 1/2:
auto correction (description see page 57)
pipe diam. corr. (description see page 58)
Note!
Each parameter that is changed must be confirmed with the RETURN key!
•the "Next" button moves you to the next screen display:
change to next page