ETA Systems ETA-ECS6RM Recording Equipment User Manual


 
– 19 – ETAsys.com
Specifications are subject to change without notice.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800-321-6699 • Fax: 800-996-3821
TROUBLESHOOTING
Note: All troubleshooting should be done by a certified electrician.
Issue 1 – ECM Module Incoming AC LED is not illuminated.
Possible Cause #1 Incoming AC mains circuit breaker has tripped due to excessive load.
Action Needed Check the AC outlet that the ETA-ECS6RM is plugged into for proper voltage. If no voltage is present check
to see if the AC outlet is on a GFI, check to see if it was tripped. If it has not been tripped trace the AC
Mains outlet back to the electrical panel and check the AC Mains breaker to see if it is tripped.
Possible Cause #2 AC mains power is OK (120V), internal 15A (ETA-15SH) and 20A (ETA-ECM20, ETA-ECM20M, ETA- 20SH)
Slow Blow fuse is blown.
Action Needed Open ECM unit and replace the fuse with a Slow Blow type.
Issue 2 – ECM module AC Fault LED is Illuminated on the ECM
Possible Cause Although the Clamping Suppression circuit virtually assures protection from most transient voltage spikes
and surges, nature has a way of occasionally creating electrical forces that are beyond the capabilities of
any device to absorb without some degree of damage. In the rare instance that this occurs, the clamping
circuit has been damaged during the suppression.
Action Needed The unit will need to be repaired or replaced. It is important to have all equipment that was connected to
that AC Mains Line be inspected for proper operation.
Note: The unit will still operate but no AC Spike or Suppression protection will be available.
Issue 3 – ECM module is set External Trigger, the Incoming AC LED is Illuminated but the Active LED is not Illuminated.
Possible Cause #1 External DCV from the ETA-ECS6RM is not connected across the “+” and “G” terminals of the ECM
module.
Possible Cause #2 External DCV voltage polarity is not correct across the “+” and “G” terminals.
Possible Cause #3 External DCV voltage is too low to activate the trigger circuit. Must be a minimum of 5VDC to activate the
ECM module. Possible short in the wiring system.
Issue 4 – ECM Active LED is not illuminated but the Incoming LED is. The Abnormal LED on the ETA-ECS6RM voltage display
is flashing “OL” and the ETA-ECS6RM Channel that is activating the ECM module Green Status LED is Flashing.
Possible Cause The AC Mains Voltage was between 101VAC and 107VAC or 127VAC and 132VAC activating the “EVS”
shutdown.
Action Needed The ETA-ECS6RM must be re-sequenced to reset the circuit. Measure the AC mains before the ECM
module. If the voltage is between 117VAC and 123VAC you may proceed to reset the ETA-ECS6RM by
restarting the start up sequence.
Note: It is important to have all equipment that was connected to that AC Mains Line inspected for proper
operation. If the problem persists, contact your local power company for the cause of unstable AC line
conditions.
ETA-ECS6RM
Electrical Control Sequencer