Turbine Installation
HONEYWELL™ Wind Turbine WT6500 Owner’s Manual - Rev 10
DC Power Wiring
TURBINE JUNCTION BOX
EARTH
GROUND
STAKE
TURBINE POLES
SEE TURBINE TO CONTROLLER SIZE
CHART ON SHEET 1
(2) #10 THWN-2 + #6 GND
¾” CONDUIT
MAX DISTANCE 3 FEET.
#4 GND
Figure 2.10 Power Wiring Diagram
Turbine Wiring and Distances
The HONEYWELL™ Wind Turbine and SMARTBOX™ Controller can be installed
at a maximum distance of 200 feet apart. The SMARTBOX™ Controller and battery
enclosure can be installed at a maximum distance of 10 feet apart.
Turbine Current Rating and Wiring
The turbine input is rated for 20 amps maximum Isc (short circuit). The recommended
wire type is #10 AWG USE-2/RHW-2 or THWN-2, 90 degrees C wire for a turbine-to-
Smart-Box distance of up to 150 feet. The wire gauge should be increased to #8 AWG
for a distance of 150-200 feet. Due to the outside location of the turbine, a 70 degree
C ambient temperature correction is recommended.
TURBINE TO CONTROLLER WIRE SIZE CHART
TURBINE WIRE MAX DISTANCE (FT) EMT CONDUIT (INCH)
#10 (#6 GND) 3/4
#8 (#4 GND) 1
150
200