HONEYWELL™ Wind Turbine WT6500 Owner’s Manual - Rev 10
Turbine Installation
Figure 2.11 Turbine Connection Location in SMARTBOX™ Controller
Turbine Over-Current Protection
The NEC/CEC requires the turbine circuit to be protected with a device rated for 125%
of the rating of the circuit. The DC-rated fuse or circuit breaker between the turbine
and the SMARTBOX™ Controller must have a maximum size of 15 (the maximum
current rating of the Smart Box).
SHOCK OR FIRE HAZARD
Over-current protection must be installed to protect the
Smart Box from short circuits and to provide a means of
disconnecting the it.
REVERSE POLARITY DAMAGE
Before making the nal DC connection or closing the DC
breaker or disconnect, check cable polarity at both the
battery and the Smart Box. Positive (+) must be connected
to positive (+). Negative(-) must be connected to negative
(-).