ICP-CC404 | Installation Guide | 22.0 Programming Sheets
90 Bosch Security Systems, Inc. | 12/08 | F01U089401-02
Location
Function
Options/Notes
Default/
Programming Entry
10 7
350 to 351
System Status – AC Fail Restore Report
Refer to page 62
Location 350: tens digit
Location 351: units digit
10 1
352 to 353
System Status – Low Battery Report
Refer to page 62
Location 352: tens digit
Location 353: units digit
10 6
354 to 355
System Status – Low Battery Restore Report
Refer to page 63
Location 354: tens digit
Location 355: units digit
6 7 12
356 to 358
System Status – Access Denied (Code Retry)
Refer to page 63
Location 356: Code retry limit (0 = unlimited)
Location 357: tens digit
Location 358: units digit
1
359
System Status Reporting Options
Refer to page 63
0 No System Status Reports allowed
1 Report to Receiver 1
2 Report to Receiver 2
4 Report to both Receiver 1 and Receiver 2
8 Report to Receiver 2 only if Receiver 1 fails
0 0 0 0 7 1 0
360 to 366
Test Report Time (Automatic)
Refer to page 63
Location 360: Hour of day (tens digit)
Location 361: Hour of day (units digit)
Location 362: Minute of day (tens digit)
Location 363: Minute of day (units digit)
Location 364: Test Report (tens digit)
Location 365: Test Report (units digit)
Location 366: Repeat interval in days
1
367
Test Reporting Dialer Options
Refer to page 64
0 No Test Reports allowed
1 Report to Receiver 1
2 Report to Receiver 2
4 Report to both Receiver 1 and Receiver 2
8 Report to Receiver 2 only if Receiver 1 fails
1 14 0 0 0 0
(Horn speaker)
1 15 1 0 0 0
(Sirens running)
368 to 397
Outputs
Refer to page 64
Output 1
(368 to 373)
Relay Output
(386 to 391)
2 7 10 2 1 3
(Fire alarm with verification)
0 13 2 1 0 1
(Entry/exit plus day alarm)
Output 2
(374 to 379)
Codepad Buzzer
(392 to 397)
6 0 6 4 0 8
(Strobe – reset after 8 hr)
Strobe Output
(380 to 385)
The first two locations (from the left) of the output definition provide the Event Code. For a complete list
of the Output Event Codes, refer to Section 16.2 Output Event Types on page 65.
The third location of the output definition is the output polarity. The options are:
0 Disabled
1 Normally open, going low
2 Normally open, pulsing low
3 Normally open, one shot low
4 Normally open, one shot low (can restart)
5 Normally open, one shot low (can reset)
6 Normally open, one shot low (alarm)
7 Normally open, latching low
8 Normally low, going open
9 Normally low, pulsing open
10 Normally low, one shot open
11 Normally low, one shot open (can restart)
12 Normally low, one shot open (can reset)
13 Normally low, one shot open (alarm)
14 Normally low, latching open
The fourth location of the output definition is the time base. The options are:
1 200 ms
2 1 sec
3 1 min
4 1 hr