Schneider Electric 400 Drums User Manual


 
10 (36), 0-004-7771-2 (GB) TAC AB, 2003-07-01
TAC Xenta 400 I/O modules 2 I/O modules in the TAC Xenta 400 series
The I/O modules are used as expansion modules for the TAC Xenta
controllers, connected to these via the common TP/FT-10 network.
The modules have different I/O configurations to suit different
applications. Some models have indicators for the digital input status
and a manual override for the digital or analog outputs. An overview of
the available models is shown below.
I/O module DI DI DO DO UI TI AO AO
TAC status override override
Xenta 411 10 - - - - - - -
Xenta 412 10 10 - - - - - -
Xenta 421 4 - 5 - - - - -
Xenta 422 4 4 5 5 - - - -
Xenta 451 - - - - 4 4 2 -
Xenta 452 - 4
1
--4422
Xenta 471 - - - - 8
2
-- -
Xenta 491 - - - - - - 8 -
Xenta 492 - - - - - - 8 8
1
Status indication only when the corresponding universal inputs (UI) are being
used as digital inputs.
2
0/4–20 mA or 0/2–10 V DC
where
DI: Digital input
DO: Digital output
UI: Universal input
TI: Thermistor input
AO: Analog output