Schneider Electric 400 Drums User Manual


 
30 (36), 0-004-7771-2 (GB) TAC AB, 2003-07-01
TAC Xenta 400 I/O modules 4 Installation
TAC Xenta 400 I/O modules
Terminals type X:
Min. cross-sectional area ...................................................0.25 mm²
Max. cable length .................................................................... 200 m
Terminals type U, connected as
a) digital inputs,
b) measurement devices using voltage signals that are not
powered via the same transformer as the I/O module or
c) measurement devices using current signal
Min. cross-sectional area ...................................................0.25 mm²
Max. cable length .................................................................... 200 m
Terminals type U, connecting measurement devices, using voltage
signals that are powered via the same transformer as the I/O
module:
Min. cross-sectional area ...................................................0.75 mm²
Max. cable length ...................................................................... 20 m
Terminals type B or U, as thermistor inputs:
Min. cross-sectional area ...................................................0.75 mm²
Max. cable length,
up to 75 °C, cross-sectional area 0.75 mm² .............................. 75 m
up to 75 °C, cross-sectional area 1.5 mm² .............................. 150 m
up to 150 °C, cross-sectional area 1.5 mm² .............................. 75 m
Terminals type K (relay outputs):
Cross-sectional area ................................................. 0.75 – 1.5 mm²
Max. cable length .................................................................... 200 m
Terminals type Y (for actuators powered via
the same transformer as the I/O module):
Min. cross-sectional area ...................................................0.75 mm²
Max. cable length
1
................................................................... 20 m
Terminals type Y (for actuators power supplied via
their own transformer, external or internal;
or when the outputs have isolated converters):
Min. cross-sectional area ...................................................0.25 mm²
Max. cable length .................................................................... 200 m
1
Some actuators allow greater cable lengths, for example:
EM52 0.5 mm² 80 m three wires
EM15LBB 0.75 mm² 80 m three wires
EM42 0.75 mm² 80 m four wires
TAC Forta 0.75 mm² 80 m four wires
TAC Forta 1.5 mm² 100 m three wires (part nos. xxxx-010)
4.3 Commissioning
Commissioning of the I/O modules is always carried out together with
the base units (TAC Xenta controllers) that they belong to.
The procedure is therefore described in the TAC Xenta 300 and 401
manuals.