LG Electronics LGENBOX-01 Drums User Manual


 
31
6 Product Specifications
6-1 AC Module
DC Input
Parameter Section Value
Power
Max. 295 W 300 W 305 W
Tolerance 3 % 3 % 3 %
Voltage
Open Circuit 39.7 V 39.8 V 40.0 V
Max Power Point 31.8 V 32.0 V 32.1 V
Current
Short Circuit 9.85 A 9.98 A 10.10 A
Max Power Point 9.28 A 9.40 A 9.52 A
Efciency
Relative Reduction < 2.0 %
Note : Relative efciency reduction in respect to irradiance.
Note : Rated electrical characteristics are within 10 percent of above gures.
PV module was measured at STC. (Standard Test Condition: Irradiation 1,000W/m
2
, Cell temp. 77ºF(25℃),
1.5AM)
AC Output
Parameter Section 240VAC 208VAC
Power
AC Continuous
1)
280W(@DC Module 295W) / 285W(@DC Module 300W) /
290W(@DC Module 305W)
Inverter Rated Continuous 305 W 300W
Voltage Rated 240 V (211 ~ 264 V) 208 V (187 ~ 229 V)
Current
Rated 1.27 A 1.44 A
Max Fault Current 77 A
Frequency
Nominal 60 Hz (59.3 ~ 60.5 Hz)
Extended
2)
57.0 Hz ~ 60.5 Hz
Power Factor > 0.95
CEC Weighted Efciency
(California Energy Commission)
96.5 % 96.0 %
Max. Number of AC Modules
3)
12 units 11 units
1)
AC Continuous = Max Input DC Power x CEC Efciency.
2)
For setting frequency rage, refer to Chapter 4-3. Conguring the Instalation App - Step 5.
3)
For details, refer to Chapter 3-10. Connecting AC Module Array to Distribution Panel.
Protection
Ground Fault Detection and Interrupt (GFDI) Applied
Fuse (Internal of the Micro Inverter)
2A
CAUTION : FOR CONTINUED PROTECTION AGAINST RISK OF FIRE,
REPLACE ONLY WITH SAME TYPE AND RATING OF FUSE.
Over Current Protection Device (OCPD)
3)
20A
3)
For details, refer to Chapter 3-10. Connecting AC Module Array to Distribution Panel.