Omega RD260A Recording Equipment User Manual


 
5 - 2
5.1 Various Modes
The recorder has three modes which are described below:
OPERATION mode
This is the mode for daily operation; when the power turns on, the recorder
automatically enters this mode. For details, see chapter 4 “DAILY OPERATION AND
MAINTENANCE”.
SET mode
In this mode, daily-used data such as alarm setpoints, date, and time are set. Pressing
the [DISP] key three seconds in the OPERATION mode changes the mode to the SET
mode.
SET UP mode
In this mode, you make settings for digital printing, alarm, burnout function and others,
also adjust the pen’s position or the position where the recorder prints dots. You can
enter this mode by turning the power on while pressing the [CH UP] ( ENT) key.
NOTE While in the SET UP mode, measurement, recording, and alarm detection are
not carried out.
Using the SETTINGS PROTECTION FUNCTION, you can protect your settings by
defining a password when you enter the SET or SET UP mode. For details on the
settings protection function, see section 7.17.
Turning the function off:
OPERATION
mode
SET mode
SETUP mode
Power ON
Power ON while pressing
the [CH UP] (ENT) key.
Mode changes to the other by pressing
the [DISP] key for three seconds.
Leaving the SET UP mode
is done by SET UP END
procedure.
Turning the function on:
DISP
3 sec.
SETUP mode
Power ON
Power ON while pressing
the [CH UP] (ENT) key.
*
1
Mode changes to the other by pressing
the [DISP] key for three seconds.
Leaving the SET UP mode
is done by SET UP END
procedure.
SETUP
Password
Password
SET mode
OPERATION
mode
*
1
*
1
QUIT