SentrySafe SPD 5.5.5 Recording Equipment User Manual


 
Sample Sequencer
Maintenance
10. Repeat steps 7 and 8 until point is calibrated.
11. Repeat steps 5 through 9 for the remaining points on the track & hold board(s).
12. The recorder calibration may also be checked by repeatedly pressing the "NEXT" key on the
Sequencer. This will verify recorder operation with the milliampere calibration signal.
13. Turn off power to the Sequencer. Remove the milliampere power source and meter.
14. Turn DIP switch SW1-3 off. This switches the Sequencer back to normal mode of operation.
15. Turn power on. Analog output calibration is complete. Re-program cycle time for desired
amount. Push START/RESET to restart the Sample Sequencer.