MPCMM0002 CMM—Safety Warnings
Intel NetStructure
®
MPCMM0002 Chassis Management Module
Hardware TPS July 2007
80 Order Number: 309247-004US
18.0 Safety Warnings
Caution: Review the following precautions to avoid personal injury and prevent damage to this
product or products to which it is connected. To avoid potential hazards, use the
product only as specified.
Read all safety information provided in the component product user manuals and
understand the precautions associated with safety symbols, written warnings, and
cautions before accessing parts or locations within the unit. Save this document for
future reference.
AC AND/OR DC POWER SAFETY WARNING: The AC and/or DC Power cord is the
unit’s main AC and/or DC disconnecting device, and must be easily accessible at all
times. Auxiliary AC and/or DC On/Off switches and/or circuit breaker switches are for
power control functions only (NOT THE MAIN DISCONNECT).
IMPORTANT
: See installation instructions before connecting to the supply.
For AC systems
, use only a power cord with a grounded plug and always make
connections to a grounded main. Each power cord must be connected to a dedicated
branch circuit.
For DC systems
, this unit relies on the building's installation for short circuit (over-
current) protection. Ensure that a Listed and Certified fuse or circuit breaker no larger
than 72VDC, 15A is used on all current carrying conductors. For permanently
connected equipment, a readily accessible disconnect shall be incorporated in the
building installation wiring. For permanent connections, use copper wire of the gauge
specified in the system's user manual.
The enclosure provides a separate Earth ground connection stud. Make the Earth
ground connection prior to applying power or peripheral connections and never
disconnect the Earth ground while power or peripheral connections exist.
To reduce the risk of electric shock from a telephone or Ethernet* system, connect the
unit's main power before making these connections. Disconnect these connections
before removing main power from the unit.
RACK MOUNT ENCLOSURE SAFETY: This unit may be intended for stationary rack
mounting. Mount in a rack designed to meet the physical strength requirements of
NEBS GR-63-CORE and NEBS GR 487. Disconnect all power sources and external
connections prior to installing or removing the unit from a rack.
System weight may be minimized prior to mounting by removing all Hot Swappable
equipment. Mount your system in a way that ensures even loading of the rack. Uneven
weight distribution can result in a hazardous condition. Secure all mounting bolts when
rack mounting the enclosure.
Warning
: Verify power cord and outlet compatibility: Use the appropriate power
cords for your power outlet configurations. Visit the following web site for additional
information: http://kropla.com/electric2.htm.