Anderson Manufacturing AV-9000 Recording Equipment User Manual


 
Section 13Edition 3
Rev G
13-6
6. Press the to advance to the next parameter, OUTPUT 1 HYSTERESIS
(only seen if OUT 1 TYPE is ON/OFF).
NOTE: Units correspond to
Units configured in Process
Variables
Cx OUT 1 HYSTERESIS
3 UNITS
Selections
0 to 999999
(decimal position = 0)
0 to 9.9999
(decimal position = 4)
7. Press the to advance to the next parameter, OUTPUT 2 HYSTERESIS (only seen if OUT 2 TYPE is ON/
OFF).
NOTE: Units correspond to
Units configured in Process
Variables
Cx OUT 2 HYSTERESIS
3 UNITS
Selections
0 to 999999
(decimal position = 0)
0 to 9.9999
(decimal position = 4)
8. Press the to advance to the next parameter, OUTPUT 1 PERCENT UPPER LIMIT (only seen if OUT 1
TYPE is PID).
Cx OUT 1 PERCENT
UPPER LIMIT 100%
Selections
1 to100
Press the to change, then or
to desired number, then press the .
Note: Hysteresis centers on the control setpoint.
Press the to change, then or
to desired choice, then press the .
Press the to change, then or
to desired number, then press the .
Note: Hysteresis centers on the control setpoint.