Chapter 5: Management with the CLU
151
Enclosure Management
From the Main menu, press 1 and Enter then 2 and Enter to access Enclosure
Management. Select the component whose performance you want to check.
Fan Speed
From the Enclosure Management menu, press 1 and Enter to access Fan
Speed.
****************Fan Speed***************
Fan # RPM Normal Operational Range
------------------------------------------------------------
1 4753 3750-5250
2 0 3750-5250
3 1917 1350-2850
4 1928 1350-2850
5 1804 1350-2850
6 1804 1350-2850
In this example, Fan 2 is not turning. This condition can cause overheating of the
VTrak subsystem. A broken fan requires replacement, even if the VTrak
temperature readings are currently normal.
Fans 1 and 2 are located on the Power Supplies. As a result, Power Supply 2
requires replacement even if the power output levels are OK.
For information on fan replacement, see .page 197.
Buzzer
From the Enclosure Management menu, press 2 and Enter to access the Buzzer
(Beeper). You can also access the Buzzer from the Main menu.
The buzzer options appear.
----------------------------------------------------
Buzzer
1. Silence Buzzer
2. Disable Buzzer
R. Return to Previous Menu
Please enter your menu choice>
4. Do one of the following:
• To silence the buzzer (for the current event only), press 1 and Enter.
• To disable the buzzer (off until enabled again), press 2 and Enter.
Silence/Disable/Enable buzzer(y/n)?>