VTrak 15110 User Manual
152
5. Press Y and Enter to confirm your choice.
If you disabled the buzzer, repeat the same procedure enable it again.
Temperature
From the Enclosure Management menu, press 3 and Enter to access
Temperature.
*********************Temperature********************
Temperature # Celsius Fahrenheit Normal Operational Range
-------------------------------------------------------------------------------
1 27 80 <= 45 Celsius
2 27 80 <= 45 Celsius
3 24 75 <= 45 Celsius
4 23 73 <= 45 Celsius
5 24 75 <= 45 Celsius
6 38 100 <= 55 Celsius
Press Enter key to return
Look for a temperature measurement above the Normal Operational Range. An
elevated temperature can be the result of a failed fan or blocked cooling
passages. Temperature #6 has a higher range because it is located directly
above the main controller board.
Voltage
From the Enclosure Management menu, press 4 and Enter to access Voltage.
******************Voltage*****************
# Voltage(volts Normal Operational Range
----------------------------------------------------------------------
1 3.39 2.96-3.63
2 5.16 4.48-5.51
3 12.09 0.76-13.19
Press Enter key to return
VTrak has three power buses, 3.3V, 5V and 12V. If a voltage is out of normal
operational range, there could be problem with the power supply(ies). Note that
bus voltage is the combined output of both power supplies. Therefore do not
condemn a power supply based on this voltage reading alone.
For information on power supply replacement, see page 196.
Battery
From the Enclosure Management menu, press 5 and Enter to access Battery.