4 - 6
4.4 Wiring
4.4.1 Wiring precautions
4
PROCEDURES AND SETTINGS BEFORE
OPERATION
(6) Take the following measures to conform the wiring to the EMC and Low
Voltage Directives.
(a) Ground the shielded twisted pair cables to a control panel with the AD75CK cable
clamp (manufactured by Mitsubishi Electric Corporation)
Figure 4.4 AD75CK cable clamp
For the AD75CK, refer to the following manual.
AD75CK-type Cable Clamping Instruction Manual
(b) The power supply line connecting to the external coincidence output power supply
module should be 10m or less long.
(c) Keep the length of the cable connected to the external devices of the QD64D2 to
30m or less.
AD75CK
In a control panel
QD64D2
20cm (7.87inch)
to 30cm (11.81inch)