Mitsubishi Electronics QD64D2 Drums User Manual


 
6
UTILITY PACKAGE (GX Configurator-CT)
6.2 Installing and Uninstalling the Utility Package
6.2.1 Handling precautions
6 - 4
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
PROCEDURES AND
SETTINGS BEFORE
OPERATION
5
FUNCTIONS
6
UTILITY PACKAGE (GX
Configurator-CT)
7
PROGRAMMING
8
TROUBLESHOOTING
For example, if multiple intelligent function modules are mounted to the remote I/O
station, configure the settings in GX Configurator so that the number of parameters
set for all the intelligent function modules does not exceed the limit of the remote I/O
station. Calculate the total number of parameter settings separately for the initial
setting and for the auto refresh setting.
The number of parameters that can be set for one module in GX Configurator-CT is
as shown below.
Example) Counting the number of parameter settings in Auto refresh setting
Table 6.2 Maximum number of settable parameters using GX Configurator
When intelligent function modules
are mounted to:
Maximum number of parameter settings
Initial setting Auto refresh setting
Q00J/Q00/Q01CPU 512 256
Q02/Q02H/Q06H/Q12H/Q25HCPU 512 256
Q02PH/Q06PH/Q12PH/Q25PHCPU 512 256
Q12PRH/Q25PRHCPU 512 256
Q00UJ/Q00U/Q01UCPU 512 256
Q02UCPU 2048 1024
Q03UD/Q04UDH/Q06UDH/Q10UDH/
Q13UDH/Q20UDH/Q26UDH/
Q03UDE/Q04UDEH/Q06UDEH/
Q10UDEH/Q13UDEH/Q20UDEH/
Q26UDEHCPU
4096 2048
Q50UDEH/Q100UDEHCPU Use prohibited Use prohibited
MELSECNET/H remote I/O station 512 256
Table 6.3 Number of settable parameters per module
Target module Initial setting Auto refresh setting
QD64D2 6 (fixed) 16 (Max.)
Figure 6.1 Numeration for the number of parameters set in Auto refresh setting
This one row is counted as one
setting.
Blank rows are not counted.
Count up all the setting items on this
screen, and add the total to the
number of settings for other intelligent
function modules to get a grand total.