Mitsumi electronic QS07J1GF11-T2 Drums User Manual


 
114
(1) Setting method
(a) Input status of data link faulty station
It can be set in the Network Operation Setting. ( Page 85, Section 7.4)
(2) Precautions
(a) When data link is stopped by users
When cyclic transmission is stopped using one of the following methods, the input status of the faulty station is
held.
CC-Link IE Field Network diagnostics ( Page 138, Section 9.4)
Link special relay (SB), link special register (SB) ( Page 221, Section 11.3 (1))
(b) Setting on a station with a data link error
When the following settings are set to "Hold" on the station where a data link error has occurred, the input
status of the own station upon error is held, regardless of setting.
"Network Operating Setting" "Output Setting During CPU STOP" ( Page 115, Section 8.2.6)
"PLC Parameter" "Intelligent Function Module Detailed Setting" "Error Time Output Mode" (only
when the station with a data link error is a standard programmable controller)
( User's manual for the CC-Link IE Field Network master/local module used)