(2) Setting example
For setting example, refer to Page 209, CHAPTER 11.
Mode
Select a master station (safety station) mode.
Two online modes are available. Select an online mode according to
the system.
• Online (Normal Mode)
• Online (High Speed Mode)
•Offline
• H/W test
• Self-loopback test
• Loop test
(Default: Online (Normal Mode))
Select a local station mode.
•Online
•Offline
• H/W test
• Self-loopback test
(Default: Online)
Item Description Setting range
Mode Description
Online (Normal Mode)
This mode performs cyclic transmission and
transient transmission without losing their inherent
speed performance. This mode is suitable for a
system that performs I/O control and analog
control, and transmits large amount of data for
management, monitoring, and diagnostics by
transient transmission.
Use this mode for general applications.
Online (High Speed
Mode)
This mode preferentially performs cyclic
transmission for high-speed communications.
Note that the maximum number of points assigned
to RWw/RWr is 256 points per local station.
In this mode, the processing speed of transient
transmission is slower than in "Online (Normal
Mode)".
Offline
Select this mode to disconnect the master/local
module from the network for stopping data link with
other stations.
H/W test
Select this mode to perform a hardware test.
( Page 60, Section 6.2.1)
Self-loopback test
Select this mode to perform a self-loopback test.
( Page 62, Section 6.2.2)
Loop test
Select this mode to perform a loop test.
( Page 67, Section 6.4.1)
Mode Description
Online
Select this mode to connect the master/local
module to the network for performing data link with
other stations.
Offline
Select this mode to disconnect the master/local
module from the network for stopping data link with
other stations.
H/W test
Select this mode to perform a hardware test.
( Page 60, Section 6.2.1)
Self-loopback test
Select this mode to perform a self-loopback test.
( Page 62, Section 6.2.2)