92
7.7 Routing Parameters
Set communication paths for transient transmission between a station in the own network and stations in other
networks.
(1) Setting procedure
1. Open the setting window in GX Developer.
Project data list [Parameter] [Network param] [Ethernet/CC IE/MELSECNET]
button
2. Set parameters in the window.
3. Click the button.
Item Description Setting range
Target network No.
Set a relay station through which data are sent to stations in other networks by
transient transmission in the own network. Up to 8 communication paths can
be set.
Set routing parameters as shown below.
Setting to transmit data to network number ● by transient transmission
1 to 239 (Default: Blank)
Relay network No. 1 to 239 (Default: Blank)
Relay station No. 0 to 120 (Default: Blank)
Ex.
No routing parameter setting is required for
network No. because the module of
network No. is mounted on the relay station.
(Relay station)
Station that needs
routing parameters
Network No.
Network No.
To go to network No. , data passes through station No. of its own network No. .
*1