Mitsumi electronic QS07J1GF11-T2 Drums User Manual


 
196
(S1)+5
Target station's
number
Specify the target station number.
(1) Station number specification
Master station: 125 (7D
H
)
Local station, intelligent device station: 1 to 120
(2) Group specification (The target station is on a network other
than a CC-Link IE Field Network.)
81
H
to A0
H
: All stations in Group No. 1 to 32
Can only be specified for clock data write.
(3) All stations specification
FF
H
: All stations on the target station network No. (excluding
own station)
Can only be specified for clock data write.
When executing instructions using the group specification or all
stations specification
• Specify "0000
H
" or "03FF
H
" for the target station CPU type
((S1)+3) ( Page 156, Section 10.2.1 (5))
• The group specification cannot be used for CC-Link IE Field
Network stations.
• Arrival confirmation as to whether data was written in the target
station cannot be used. To check whether data was written
normally, check the clock data of the write target station.
• Clock data cannot be written to the station with the station number
already in use or the station with no station number setting. Correct
the error then execute the instruction.
125 (7D
H
)
1 to 120
81
H
to A0
H
FF
H
User
(S1)+6 Unused 0User
(S1)+7
Number of
resends
During instruction execution
For the case where the instruction is not completed within the
monitoring time specified by (S1)+8, specify the number of
times the instruction is resent.
0 to 15 User
When the instruction is completed
The number of resends (result) is stored.
System
(S1)+8
Arrival monitoring
time
Specify the monitoring time until instruction completion.
If the instruction is not completed within the specified time, the
instruction is resent for the number of resends specified by (S1)+7.
0: 10 seconds
1 to 32767: 1 to 32767 seconds
0 to 32767 User
(S1)+9
Request data
length
Specify the request data count (word).
(Word count of data to be stored in own station start device (S2)
where request data is stored)
2: Clock data read
6: Clock data write
2, 6 User
(S1)+10
Response data
length
Store the response data count (word).
(Word count of data to be stored in own station start device (D1)
where response data is stored)
6: Clock data read
2: Clock data write
System
Device Item Setting data Setting range Set by
Group No. 1: 81
H
Group No. 2: 82
H
Group No. 32: A0
H