(1) Procedure
The following describes a procedure for identifying the cause of an error and the action when the master station
is a safety programmable controller.
When the master station is a standard programmable controller, refer to the following.
User’s manual for the CC-Link IE Field Network master/local module used
If data link cannot be performed even though no error is indicated in the "System Monitor" window, select the master/local
module, and click the button. ( Page 238, Section 12.2 (1) (b))
1. Connect GX Developer to the safety CPU module,
and open the "System Monitor" window.
[Diagnostics] [System monitor]
2. Select the module in which an error has occurred.
When a module other than the master/local module is
selected
Page 237, Section 12.2 (1) (a)
When the selected module is the master/local module
Page 238, Section 12.2 (1) (b)