CHAPTER 10 DEDICATED INSTRUCTIONS
10
10.6 JP/GP.WRITE (Writing Data to the Programmable Controller on Another Station)
*1 If Completion status ((S1)+1) is "Channel in use (dedicated instruction) (error codes: D25A
H
and D25B
H
)", data is not
stored.
(b) Start device of the own station where data to be written is stored
Specify the start device of the own station that stores data to be written.
(c) Start device of the target station where data is to be written
If the device setting in PLC Parameter is different between the own and target stations, use "(D1)" (with double-
quotation marks) to specify.
Specify the start device (D1) of the target station, within the available range so that the write data can be
stored.
When the area addressed D150 or higher of the target station CPU is already used
(S1)+11 Clock set flag
The valid or invalid status of data after (S1)+12 is stored.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
0: Invalid
1: Valid
System
(S1)+12 to
(S1)+15
Clock data of
abnormal end
Clock data of abnormal end is stored in BCD format.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
When the target station is QnACPU, 00
H
is stored in the year (the
first two digits of the year).
System
(S1)+16
Error-detected
station's network
No.*
1
The network No. of the station in which an error was detected is
stored.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
1 to 239: Network No.
System
(S1)+17
Error-detected
station number*
1
The station number of the station in which an error was detected is
stored.
(Data is stored when "1: Data at the time of abnormal end is set in
the area starting from (S1)+11." is set in the abnormal end type in
(S1)+0.) The stored data is not cleared even if the dedicated
instruction is normally completed.
Master station: 125 (7D
H
)
Local station, intelligent device station: 1 to 120
System
Device Item Setting data Setting range Set by
(S1)+12
(S1)+13
(S1)+14
(S1)+15
Month (01
H to 12H)
Hour (00
H to 23H)
Second (00
H to 59H)
Day (01
H to 31H)
Minute (00
H to 59H)
00
H (Sun.) to 06H (Sat.)
Day of week (00
H
to 06
H
)
Year (00
H
to 99
H
), first 2 digits
Year (00
H
to 99
H
), last 2 digits
b15 b8 b7 b0
Ex.