248
D0C1
H
Reserved station cancellation failed
(another process in progress)
Wait for a while, and cancel the reserved station setting again.
D0C2
H
Data link stop failed (another process
in progress)
Wait for a while, and instruct the data link stop again.
D0C3
H
Data link start failed (another process
in progress)
Wait for a while, and instruct the data link start again.
D0C4
H
Temporary error invalid station setting
failed (another process in progress)
Wait for a while, and set the temporary error invalid station again.
D0C5
H
Temporary error invalid station
cancellation failed (another process in
progress)
Wait for a while, and cancel the temporary error invalid station setting again.
D0C6
H
Another station number change failed
(another process in progress)
Wait for a while, and set the station number of another station.
D0D0
H
Another station number setting failed
(another process in progress)
Wait for a while, and set the station number of another station.
D0E0
H
Station type mismatch
In "Network Configuration Setting" for the master station, change the station
type to that of the own station.
D0E1
H
Own station reserved
• In "Network Configuration Setting" for the master station, cancel the
reserved station setting.
• Change the station number of the own station to a station number that is
not reserved.
D0E2
H
Station No. duplication (own station)
• Set a unique station number.
• After taking the above action, power off and on all the stations that
detected the station number duplication error, or reset them.
D0E3
H
Own station No. out of range
Add information of the own station to "Network Configuration Setting" of the
master station.
D0E4
H
Multiple master stations (including own
station)
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• After taking the above action, power off and on all the stations that
detected this error, or reset them.
D0F0
H
Network module failure
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D100
H
to D101
H
Network module failure
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D110
H
to D113
H
Network module failure
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
D200
H
Transient data received twice
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• If the request source is on another network, check if the routing
parameters are correctly set.
Error code Error Action