Mitsumi electronic QS07J1GF11-T2 Drums User Manual


 
82
RX/RY Setting
Set assignment for RX/RY for each slave station. ( Page 103,
Section 8.2.1)
Enter values in increments of 16 points (Start: 0
H
, End:
F
H
).
• Points:
• Device number: 0 to 3FFF
H
(Default: Blank)
RWw/RWr Setting
Set assignment for RWw/RWr in increments of 4 points for each slave
station. ( Page 103, Section 8.2.1)
• Points:
• Device number: 0 to 1FFF
H
(Default: Blank)
Refresh Device
Link devices of the master/local module to be transferred by link
refresh and the transfer target safety CPU module devices are
displayed.
This item is displayed when refresh parameters have been set.
( Page 86, Section 7.5)
Reserved/Error Invalid
Station
Set this item to reserve the slave station or to set the slave station as
an error invalid station. ( Page 119, Section 8.4, Page 120,
Section 8.5)
• No Setting
The slave station is connected to the network.
• Reserved Station
The slave station is reserved for future expansion. By reserving a
slave station, link device assignment will not change even if the
slave station is added or the reservation is cancelled. Therefore, the
program needs not to be modified. Physical connection of the slave
station is not required.
• Invalid Station
Even if a slave station is disconnected during data link, the master
station (safety station) will not detect the slave station as a faulty
station. However, if a local station (safety station) set as an error
invalid station or a temporary error invalid station is disconnected,
an error will occur in safety communication with the disconnected
station.
• No Setting
• Reserved Station
• Invalid Station
(Default: Blank)
Alias Enter the name of a device on the slave station if required.
Up to 8 characters
(Default: Blank)
Comment Enter the comment of the slave station if required.
Up to 32 characters
(Default: Blank)
Item Description Setting range
Station Type
Setting
range
Local Station, Intelligent
Device Station
16 to 2048
Remote Device Station 16 to 128
Remote I/O Station 16 to 64
Station Type
Setting
range
Local Station, Intelligent
Device Station
4 to 1024
Remote Device Station 4 to 64
Remote I/O Station
Cannot be
set.